Daily Real Efficiency vs. Cassandra Hybrid AI Digital Twin
Hover any day to inspect exact expected vs. measured efficiency and daily excess electricity
Daily Chiller Health Calendar Matrix
Each day compares real efficiency against the AI Digital Twin • White ring = onset • Teal ring = CUSUM alert
Daily Excess Electrical Draw — Twin Compressor Split
Measured kW minus Digital Twin prediction • Faulted stage spikes while control stage tracks near 0 kW
Bayesian Root-Cause Likelihood
Includes explicit honest reserve for unmeasured internal sensors
Compressor C2
Excess Power by Load Band
Low-load peaking confirms internal bypass over fouling or leak
Ruled-Out Faults — Cleared Subsystems
Contradicted by multi-sensor physics so technicians skip unnecessary work
15-Minute On-Site Technician Verification Checklist
Advisory Confidence: Medium — field verification confirms root cause
Physics Evidence & Live 2D Plant Digital Twin (For HVAC Engineers) Click to Expand Radar, Pressures & P&ID
Live 2D Chiller Refrigeration Loop & Fault Localization Map
Fault-window telemetry mapped directly onto heat exchangers, pipes, and twin compressors
6-Axis Twin-Stage Fault Severity Radar
Normalized anomaly shift: Healthy C1 (Sage) vs. Faulted C2 (Coral)
Direct Head-to-Head A/B Metrics
Includes back-to-back C1 ↔ C2 switches within 2 hours at matched load
Load-Stratified Excess Power & Pressure Divergence
Suction pressure rises (+51 mbar) while discharge dips (−24 mbar) at low load
Thermodynamic Physics Decoder
Why internal bypass beats competing faults
Hot discharge gas recycles to suction → fixed parasitic power peaks at low load, pushing suction P up and discharge P down.
Would push discharge pressure strongly UP and worsen at high cooling loads.
Would starve the evaporator and pull suction pressure DOWN — opposite of measured +51 mbar rise.
Appeared cleanly right after a 34-hour compressor idle stretch — classic sticking unloader or bypass valve.
Monthly Avoidable Electricity Cost Waterfall
Updates live with your selected currency and tariff rate
Annualized Fleet Risk Scaling*
Projected annual impact if the same single-stage fault affects multiple chillers
| Tariff Rate | 1 Chiller / yr | 5 Chillers / yr | 15 Chillers / yr |
|---|
Scope 2 Decarbonization Impact
Early fault remediation eliminates silent wasted kWh and delivers auditable carbon reduction.
Cumulative Avoidable CO₂ Emissions: Early Fix vs. Unaddressed
Shaded teal wedge shows preventable Scope 2 emissions after the Day 3 alert
Computed directly from measured excess kWh above the healthy digital twin.
Using EU/UK average 122 g CO₂/km passenger vehicle factor.
Using ~21.7 kg CO₂/yr absorption per mature urban tree.
Multi-Year Chiller Lifecycle Health & Fault Recurrence (2022 – 2025)
Monthly Real EER deviation vs. 2022 Digital Twin — shows Winter 1 fault recurring even harder the next winter when unfixed
Next-Gen Hybrid AI Model Arena (Blind Out-of-Sample)
Power prediction error (kW RMSE) vs. actual +3.81 kW silent fault signal
Predicted vs. Measured Power (R² = 0.9959)
Unseen operating hours tightly hugging the y = x thermodynamic diagonal
Executive Board & Maintenance Handover Sheet
Ready for client reviews, facility management sign-off, and PDF archival